For millimeter-wave radar, the measurement accuracy is up to ± 2mm, and the minimum measurement blind area is 0.05m.
1.Smaller antenna size, to meet the more working conditions of the measurement.
2.Multiple lens antennas, smaller emission angle, more concentrated energy, stronger echo signal, under the same industrial and mining conditions, compared to the Other radar products have higher reliability.
3.It is more penetrating, and can also be used normally with adhesion and condensation.
4.The dynamic signal range is larger and is more stable for measurements of low dielectric constant media.
5.A variety of measurement modes, and the radar response in the rapid measurement mod
RD80G electrical connection
service voltage
(4~20) mA / HART (two-wire system) power power supply and output current signal
share a two-core shield cable. Refer to the technical
data for the specific power supply voltage range. (4~20) mA (four-wire / six-wire) power supply needs to be supplied separately, power
supply and current signal using a four-core shielding
cable (current signal and RS485 interface can be output
simultaneously, and output needs using a six-core
shielding cable). The RS485 / Modbus power supply shall be supplied separately, with a four-core
shielded cable
(The current signal and RS485 interface can be
simultaneously output with a six-core shielded cable).

Safety guidance
Please follow the local electrical installation regulations!
Please follow the local regulations for personnel health and safety. All operation of
instrument electrical components must be done by properly trained professionals. Please check the nameplate of the instrument to ensure that the product specifications
meet your requirements. Ensure that the supply voltage is consistent with the requirements
on the instrument nameplate.
levels of protection
This instrument fully meets the requirements of protection grade IP66 / 67, please ensure
that the cable seal head is waterproof.as illustrated in following figure:

How to ensure that the installation meets the IP67 requirements:
Make sure that the sealing head is not damaged.
Make sure that the cable is not damaged.
Please ensure that the cables used comply with the electrical connection specification.
Before entering the electrical interface, bend the cable down to ensure that the water does not flow into the housing, see ①
Tighten the cable seal head, see ②
Please blind the unused electrical interface, see ③